Power variable analysis and great communication capabilities: this is the strength of PQT 90
• Energies-water-gas and instantaneous variables readable
on the display of your GSM mobile phone giving you
maximum control freedom, saving time and money.
• Alarms transmitted as soon as they occur via GSM or ana-
logue modem, notifying the plant abnormal conditions.
• Data logging and stamping of up to 8 programmable instan-
taneous variables for a time duration up to 90 weeks wi t h
date and time references to build up the history of your
electrical installation.
• PqtSoft Network communication software to download,
manually or automatically (via RS485-analogue modem
GSM modem), up to 2Mb data stored in the PQT 90.
This information can be plotted simply in an Excel
spreadsheet.
• Pqt Soft Remote to easily download or upload the
programming parameters from a PQT 90 to a PC and viceversa.
• Continuous data stamping and communication: RS232,
RS485, modem, GSM.
• Powerful data acquisition by means of PqtSoft and mobile
phones wherever you are.
Main variables
Variables that can be managed by PQT 90
System Average Min RS485 Analogue out
V
LL
,V
LN
V asymmetry
A
An
Hz
VA
var
W
PF
+kWh (*)
-kWh (*)
+kvarh (*)
-kvarh (*)
GAS (*)
H
2O
THD (A-V)
THD even (A-V)
THD odd (A-V)
Single harmonic
Single ph Max Alarm Out Pulse
Official watt-hour meter interface. The 3 interfacing methods of PQT 90 are:
• Direct measurement for the power quality analysis (LV or MV/HV connection).
• Indirect energy and power measurements by means of official Watt-hour meters
(LV or MV/HV connection).
• Direct measurements of the instantaneous variables (LV connection) and indirect
measurements of the energy variables (LV or MV/HV connection).
(*) Total and time-period energies
PqtKit the wireless solution of PQT ...