ANALOGUE RETRANSMISSION (ON REQUEST)
From 0 to 20 mADC / from 0 to 10 VDC, programmable within the whole
range of retransmission;
Accuracy and response time: ± 0.3% F.S. (@ 25°C) / 500 ms (filter
excluded);
Temperature drift: ± 200 ppm/°C
Load: output 0 to 20mA: 500 , output 0 to 10V: 10 k
Insulation: by means of optocouplers, 500VRMS between output and
measuring inputs, 2000VRMS between output and power-supply input.
SERIAL RETRANSMISSION (ON REQUEST)
RS485; multidrop: one-way (STD); bidirectional (on request); 2 or 4
wires; max. distance 1200m; termination and/or line bias directly on the
instrument; 255 programmable addresses; data format: 1 start bit, 8 data
bit, no parity, 1 stop bit; baud rate: 1200, 2400, 4800 and 9600 baud
selectable by key-pad; protocol according to the standard MODBUS;
One-way communication:
dynamic data (reading only): measurement, valley data, peak data,
alarm status;
Static data (reading/writing): all programming data.
Bidirectional communication:
dynamic data (reading only): measurement, valley data, peak data,
alarm status;
Static data (reading/writing): all programming data, reset of peak and
valley data, reset of alarm set-points with latch.
Insulation: by means of optocouplers, 500VRMS between output and
measuring inputs, 2000VRMS between output and power supply inputs