ENGLISH
programming of the scales: electrical scale, displayed scale and
decimal point position;
programming of all the parameters relating to the first set-point;
programming of all the parameters relating to the second set-point;
programming of all the parameters relating to the software filter;
programming of all the parameters relating to the analogue retransmis-
sion (when present);
programming of all the parameters relating to the serial retransmission
(when present).
TECHNICAL FEATURES
ACCURACY (VOLTAGE)
± 0.1 % F.S., ± 1 dgt (@ 25°C);
TRMS ± 0.2 % F.S., ± 2 dgt (@ 25°C)
ACCURACY (CURRENT)
± 0.1 % F.S., ± 2 dgt (@ 25°C);
TRMS ± 0.2 % F.S., ± 2 dgt (@ 25°C)
ACCURACY (RTD/ TEMPERATURE)
Pt100/Pt1000: ± 0.15 % F.S., ± 2 dgt (@ 25 °C);
Ni100: ± 0.5 % F.S., ± 1 dgt (@ 25 °C);
: ± 0.1 % F.S., ± 1 dgt (@ 25°C).
ACCURACY (TC TEMPERATURE)
± 0.2 % F.S., ± 2 dgt (@ 25 °C), from -50°C to the higher limit of the input range
TEMPERATURE DRIFT (VOLTAGE)
DC measurement: ± 150 ppm/°C;
AC measurement: ± 200 ppm/°C.
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · [email protected]