CARLO GAVAZZI EN61036 Manual de Instruções Página 82

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 84
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 81
82
Technical features
Users page
77
Software functions
72
84
83
Harmonic analysis
Analysis principle: FFT.
Harmonic measurement: current, up to the 50
th
harmonic;
voltage, up to the 50
th
harmonic.
Type of harmonics:
THD (VL1) THD odd (VL1) THD even (VL1).
The same is for the other phases:
L2, L3. THD (AL1) THD odd (AL1) THD even (AL1).
The same is for the other phases: L2, L3.
Harmonic phase angle: the instrument measures the angle
between the single harmonic of V and the single harmon-
ic of I of the same order. According to the value of the
electrical angle, it is possible to know if the distortion is
absorbed or generated.
Note: if the system has 3 wires the angle cannot be measured.
Harmonic details: the harmonic contents is displayed as a
graph showing the whole harmonic spectrum.
This value is also given as a numerical information:
THD % / RMS value; THD odd % / RMS value; THD odd % /
RMS value / single harmonics in % / RMS value.
System: the harmonic distortion can be measured in single-
phase, 3-wire or 4-wire systems. Tw: 0.02.
Vista de página 81
1 2 ... 77 78 79 80 81 82 83 84

Comentários a estes Manuais

Sem comentários