CARLO GAVAZZI EN61036 Manual de Instruções Página 77

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 84
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 76
77
Technical features
General specifications
75
RS232
72
81
83
Alarm outputs (on request)
Number of set-points: up to 4, independent.
Alarm type: up alarm, down alarm, with or without latch,
phase asymmetry, phase loss, neutral loss.
Monitoring of the variables: all the variables listed in the
paragraph List of the connectable variables.
Set-point adjustment: 0 to 100% of the electrical scale.
Hysteresis: 0 to 100% of the electrical scale.
On-time delay: 0 to 255 s.
Relay status: selectable: normally de-energized or normal-
ly energized
Output type: relay, SPDT, AC 1-8A, 250VAC, DC 12-5A,
24VDC, AC 15-2.5A, 250VAC, DC 13-2.5A, 24VDC
Min. response time: 150 ms, filters excluded, FFT
excluded, set-point on-time delay: 0s.
Insulation: 4000 V
RMS
output to measuring inputs, 4000
V
RMS
output to power supply input. Notes: the outputs can
be either open collector type or relay type (for the relay out-
put refer to the specifications described in the alarm out-
puts section).
Software functions
Password: numeric code of max. 3 digits; 2 protection lev-
els of the programming data.
1st level: password 0, no protection.
2nd level: password from 1 to 499, all data are protected.
Note: by entering in the programming mode by means of
password, the measurement is inhibited.
Operating mode selection: direct measurements for the
Vista de página 76
1 2 ... 72 73 74 75 76 77 78 79 80 81 82 83 84

Comentários a estes Manuais

Sem comentários