Outputs / Other settings
Modem
43
Counters reset
44
50
55
Type: type of alarm: up alarm (MAX); down alarm (MIN); up
alarm with latch (UP L): in this case the reset of the output
can only be manual; down alarm with latch (D.L.): in this
case the reset of the output can only be manual; down
alarm with disabling at power ON (D.DO). Choose the
desired alarm type by means of the and keys and
confirm it with .
Set on: ON-alarm set-point. Select the value of the vari-
able by means of the and keys and confirm it with
.
Set off: OFF-alarm set-point. Select the value of the vari-
able by means of the and keys and confirm it with
.
Out: Normally energized alarm (NE) or normally de-ener-
gized alarm (ND). Choose the desired function by means of
the and keys and confirm it with .
Delay: delay on alarm activation. Select the desired delay
value in seconds by means of the and keys and
confirm it with .
S
S
S
S
S
Diagnostic
In a 3-phase unbalanced-load
system, this function controls the
S
presence of the neutral connection. If the connection to the
neutral is not detected, the instrument activates an alarm.
Select DIAGNOSTIC by means of the and keys,
then press to confirm it. To reset your choice and go
back to the main menu, press .
F
S