CARLO GAVAZZI WM24-96 - PROGRAMMING Manual do Utilizador Página 7

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 42
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 6
6
To begin with
tot-Prd
4
8
8
The energy meter pages are different according to the set-
ting of the instrument (see energy meter menu on pag.13).
If you choose “tot” the instrument displays:
Generated capacitive reactive
energy: integration of the sum of
single phase reactive powers of
quadrant 4 only.
Consumed capacitive reactive
energy: integration of the sum of
single phase reactive powers of
quadrant 2 only.
Generated inductive reactive
energy: integration of the sum of
single phase reactive powers of
quadrant 3 only.
Consumed inductive reactive
energy: integration of the sum of
single phase reactive powers of
quadrant 1 only.
Generated active energy: integra-
tion of the sum of single phase
negative active powers only.
Vista de página 6