Technical features
53
Digital outputs
60
56
64
Three-phase connections
RANGE (IMPEDANCE):
AV5:
58V/100V (>500k) - 1ADC (
0.3VA)
58V/100V (>500k) - 5ADC (
0.3VA)
240V/415V (>500k) - 1ADC (
0.3VA)
240V/415V (>500k) - 5ADC (
0.3VA)
AV7:
100/170V (>500k) - 1ADC (0.3VA)
110/170V (>500k) - 5ADC (0.3VA)
400/690V (>500k) - 1ADC (0.3VA)
400/690V (>500k) - 5ADC (0.3VA)
FREQUENCY RANGE: 40 to 440 Hz
Overload protection
Continuous: voltage/current
AV5: 300VLN/520VLL/6A;
AV7: 480VLN/830VLL/6A
For 1s: voltage/current
AV5: 600VLN/1040VLL/120A;
AV7: 960VLN/1660VLL/120A
Keypad
Four keys: to enter the programming phase and confirm
the password, UP and DOWN to program the
values / select the functions and scroll the pages, for
special functions.
Output specifications
ANALOGUE OUTPUTS (on request):
Number of outputs: up to 4 (on request)
Accuracy: ±0.2% f.s.; (@ 25°C ±5°C, R.H.
60% non-
condensing)
Range: 0 to 20mADC, 0 to ±20mADC,