19
Useful information
Reset of the meters
17
23
List of the variables
23
The variables measured by the instrument are
correct if the polarities of the inputs have
been observed (as shown in the figure be-
low); if not, measuring and retransmission
errors may occur due to the wrong direction
of the current flowing in the primary / second-
ary of the connected current transformer.
■
Setting Examples
Example 1 “Analogue output”: take the measure of a power
consumed up to 100kW, and retransmit it with a signal from 4
to 20 mA; the module to be used is AO2920 (from 0 to 20mA),
the instrument must be set as follows:
• VAr: (variable), WΣ (system active power)
• LoE: (minimum electrical scale) 0.0 K; the K and M multiples
are automatically selected by the instrument according to
the selected VT and CT values;
• HiE: (maximum electrical scale) 100.0 K; the K and M
multiples are automatically selected by the instrument ac-
cording to the selected VT and CT values;
• LoA: (minimum electrical scale of the analogue output)
20.0% for 4mA, the calculation to be carried out is: (mini-
mum output value/ full scale output value)*100 = (4mA/
20mA)*100 = 20%
• HiA: (maximum electrical scale of the analogue output)
100.0% for 20mA, the calculation to be carried out is:
(maximum output value / full scale output value)*100 =
(20mA/20mA)*100 =100%